- SOLARWATT Battery vision
- Installation
- Installation of DDSU 666 electricity meter (single-phase)
Installation of DDSU 666 electricity meter (single-phase)
This page describes the installation and connection of the single-phase meter DDSU 666. The meter is supplied with the Inverter vision one. However, DO NOT use it in 3-phase networks. Order the three-phase meter DTSU 666 for use in three-phase networks.
Technical data
Dimensions: 100 x 36 x 65.5 mm (2 HP)
Max. Current: one CT terminal can be used for a measuring range of up to 100 A
CT terminal cable length: 6 m (can be cut to size or extended up to 15 m)
Max. Distance to the inverter: 100 m
Installing the meter
Observe all Safety Instructions and requirements for the installer.
The meter is included with the Inverter vision one.
However, DO NOT use it in 3-phase networks. Order the three-phase meter DTSU 666 for use in three-phase grids.
You can find the three-phase meter in the Solarwatt webshop here.
When installing the meter, please refer to the wiring diagrams provided by Solarwatt Wiring diagrams for single-phase and three-phase grids.
- Hook the meter onto the top edge of the top-hat rail in the house connection box and press down until it clicks into place
The voltage is measured via the direct connections of the DDSU 666:
- PIN 3 -> N Un
- PIN 4 -> L1 U1
Current measurement is always carried out via the CT terminal supplied, which is connected to phase L1 of the domestic installation.
The CT terminal must be positioned in the switch cabinet so that the total current can be measured before transfer to the domestic electricity meter.
A CT terminal can be used for a measuring range of up to 100 A.
DDSU current and voltage measurement - pin assignment
Pin of the meter | Port/device | Conductor cross section | Outer diameter | |
direct voltage measurement | 3 | L1 | 4 mm2 - 25 mm2 multi-core outdoor copper cable | 5 - 10 mm |
4 | N | |||
Current measurement via CT terminal | 9 | I* (white) | - | - |
10 | I (blue) |
- Connecting the cable for voltage measurement
- Connect the cable for current measurement
- only then connect the CT terminal
The cable length of the CT terminal is 6 m. If the cable is too long, it can be cut to length. If the cable is too short, it can be extended up to 15 m.
The connection for communication with the Inverter one is made via the direct connections 24 and 25.
The meter adapter is included in the scope of delivery of the Inverter one.
- Connecting the meter adapter for the connector to the inverter
- Wire end ferrules are only necessary if stranded wires are used
- Connect the meter to the inverter using the meter adapter
DDSU communication - pin assignment
Pin of the meter | Port/device | Conductor cross section | Outer diameter | |
Communication | 24 | Pin 1 Meter adapter on inverter | 0.25 mm2 - 1.5 mm2 shielded, two-core twisted outdoor cable, min. Cat 5e | 4 mm - 11 mm |
25 | Pin 2 Meter adapter on the inverter | |||
5 | Pin 485A on the SOLARWATT Charger (optional) | |||
6 | Pin 485B on the SOLARWATT Charger (optional) |