- SOLARWATT Battery vision
- Installation
- Installation of electricity meter DTSU 666 (three-phase)
Installation of electricity meter DTSU 666 (three-phase)
This page describes the installation and connection of the three-phase meter DTSU 666.
Table of contents
Overview of DDSU counters
Technical data
Dimensions: 100 x 72 x 65.5 mm (4 HP)
Max. Current: one CT terminal can be used for a measuring range of up to 100 A
CT terminal cable length: 6 m (can be cut to size or extended up to 15 m)
Max. Distance to the inverter: 100 m
Installation of the meter with a THREE inverter in the three-phase grid
Observe all Safety Instructions and requirements for the installer.
The Inverter vision three is supplied with the DTSU 666 duo RS485 CT three-phase electricity meter (Solarwatt version) for recording excess electricity and electricity consumption.
When installing the meter, please refer to the wiring diagrams provided by Solarwatt for single-phase and Wiring diagrams for single-phase and three-phase grids provided by Solarwatt.
- Hook the meter onto the top edge of the top-hat rail in the house connection box and press down until it clicks into place
The voltage is measured via the direct connections of the DTSU 666:
- PIN 3 -> L1 Ua
- PIN 6 -> L2 Ub
- PIN 9 -> L3 Ub
- PIN10 -> N Un
The current is always measured via the enclosed CT terminals, which are connected to phase L1, L2 and L3 of the domestic installation.
The CT terminals must be positioned in the switch cabinet so that the total current can be measured before transfer to the domestic electricity meter.
A CT terminal can be used for a measuring range of up to 100 A.
DTSU current and voltage measurement - pin assignment
Pin of the meter | Port/device | Conductor cross section | Outer diameter | ||
direct voltage measurement | 3 | L1 | 4 mm2 - 25 mm2 multi-core outdoor copper cable | 5 - 10 mm | |
6 | L2 | ||||
9 | L3 | ||||
10 | N | ||||
Current measurement via CT terminal | 13 | Ia* (white) | yellow | - | - |
14 | Ia (blue) | ||||
16 | Ib* (white) | green | |||
17 | Ib (blue) | ||||
19 | Ic* (white) | red | |||
21 | Ic (blue) |
- Connecting the cable for voltage measurement
- Connect the cable for current measurement
- only then connect the CT terminals
The connection for communication with the Inverter three is made via the direct connections 24 and 25.
- Configure the RJ45 plug for the connector with the Inverter vision three inverter
- attach a waterproof plug housing (included in the scope of delivery of the inverter) to the plug on the inverter side for protection and mechanical strain relief
- Connect the meter to the inverter using the RJ45 plug
DTSU and Inverter ONE communication - pin assignment
Pin of the meter | Port/device | Conductor cross section | Outer diameter | ||
Outer diameter Communication | 24 | Pin 2 Counter adapter on inverter | 0.25 mm2 - 1.5 mm2 shielded, two-core twisted outdoor cable, min. Cat. 5e | 4 mm - 11 mm | |
25 | Pin 1 Counter adapter on inverter | ||||
5 | Pin 485A on the SOLARWATT Charger (optional) | ||||
6 | Pin 485B on the SOLARWATT Charger (optional) |
Installing the meter with an Inverter ONE in the three-phase grid
Observe all Safety Instructions and requirements for the installer.
The three-phase electricity meter DTSU 666 duo RS485 CT (Solarwatt version) MUST be installed when using the SOLARWATT Inverter vision one in three-phase grids. ATTENTION: this meter is NOT part of the scope of delivery for the Inverter one. It is only included in the scope of delivery of the Inverter three.
You must order the three-phase meter separately from Solarwatt for use in the three-phase grid.
You can find the three-phase meter in the Solarwatt webshop here.
For the installation of the meter, please refer to the wiring diagrams provided by Solarwatt Wiring diagrams for single-phase and three-phase grids.
- Hook the meter onto the top edge of the top-hat rail in the house connection box and press down until it clicks into place
The voltage is measured via the direct connections of the DTSU 666:
- PIN 3 -> L1 Ua
- PIN 6 -> L2 Ub
- PIN 9 -> L3 Ub
- PIN10 -> N Un
The current is always measured via the enclosed CT terminals, which are connected to phase L1, L2 and L3 of the domestic installation.
The CT terminals must be positioned in the switch cabinet so that the total current can be measured before transfer to the domestic electricity meter.
A CT terminal can be used for a measuring range of up to 100 A.
DTSU current and voltage measurement - pin assignment
Pin of the meter | Port/device | Conductor cross section | Outer diameter | ||
direct voltage measurement | 3 | L1 | 4 mm2 - 25 mm2 multi-core outdoor copper cable | 5 - 10 mm | |
6 | L2 | ||||
9 | L3 | ||||
10 | N | ||||
Current measurement via CT terminal | 13 | Ia* (white) | yellow | - | - |
14 | Ia (blue) | ||||
16 | Ib* (white) | green | |||
17 | Ib (blue) | ||||
19 | Ic* (white) | red | |||
21 | Ic (blue) |
- Connecting the cable for voltage measurement
- Connect the cable for current measurement
- only then connect the CT terminals
The cable length of the CT terminal is 6 m. If the cable is too long, it can be cut to length. If the cable is too short, it can be extended up to 15 m.
The connection for communication with the Inverter one is made via the direct connections 24 and 25.
The meter adapter is included in the scope of delivery of the Inverter one.
- Configure the meter adapter for the connector with the Inverter vision one inverter.
- Wire end ferrules are only necessary if stranded wires are used
- Connect the meter to the inverter using the meter adapter
DTSU and Inverter ONE communication - pin assignment
Pin of the meter | Port/device | Conductor cross section | Outer diameter | ||
Outer diameter Communication | 24 | Pin 1 Counter adapter on inverter | 0.25 mm2 - 1.5 mm2 shielded, two-core twisted outdoor cable, min. Cat. 5e | 4 mm - 11 mm | |
25 | Pin 2 Counter adapter on inverter | ||||
5 | Pin 485A on the SOLARWATT Charger (optional) | ||||
6 | Pin 485B on the SOLARWATT Charger (optional) |