Cable requirements and bending radii

Danger

Ensure that the mains cable connected to the inverter is connected vertically and that the vertical length is greater than 30 cm. If the cable is kinked near the terminals, this can lead to poor cable contact and burnt-out terminals.

DANGER

Ensure that the battery cable is installed vertically downwards between the inverter and battery. The cable must not kink in the first 30 cm from the inverter, as this can lead to poor contact and consequently to burning contacts.

AC-GRID

Inverter vision one is designed for operation in the single-phase mains, voltage range 220/230/240 V, frequency 50/60Hz.
Other technical requirements must comply with the requirements of the local public grid.

Use a 3-core AC cable for the AC grid connection.

The AC grid connection is suitable for a cable cross-section of 4 mm² to 16 mm².

Use a 3-core AC cable for the AC-BACKUP connection.

The AC-BACKUP connection is suitable for a cable cross-section of up to 4 mm².

AC-GRID

Inverter vision one is designed for operation in the single-phase mains, voltage range 220/230/240 V, frequency 50/60Hz.
Other technical requirements must comply with the requirements of the local public grid.

Use a 3-core AC cable for the AC grid connection.

The AC grid connection is suitable for a cable cross-section of 4 mm² to 16 mm².

Cable requirements: flexible PV cables, 4 - 6 mm², sheath diameter 4.93 to 6 mm, MC4 from Stäubli